devices shall be created with a simple table and graphical user interface supported by
images of major manufacturers.
e. Copy to and Move functions shall be supported in patch.
f. RDM discovery and device monitoring shall be supported.
4. Setup/Browser
a. Setup shall access system, show and desk configurations.
b. The browser shall access show data storage, import, export, print to .pdf and clear
functions, as well as show data utilities.
E. Dimmer Monitoring and Configuration
1. The lighting control system shall provide communication with an ETC Sensor+, Sensor3 or
FDX dimming system for remote monitoring and configuration of show specific functions from
within the console application.
2. Circuit level configuration and monitoring functions shall include but not be limited to:
a. Control mode (dimmable, switched, latch-lock, always on, off or fluorescent).
b. Curves
c. Control threshold
d. Min and Max Scale Voltage
e. Preheat
f. Scale load
3. Rack Status messages shall include but not be limited to:
a. State of UL924 panic closure
b. DMX port error/failure
c. Network error/failure
d. A, B, C Phase below 90 or above 139 volts and headroom warning
e. Ambient temperatures out of range.
4. Circuit status shall include but not be limited to:
a. Module type and location
b. Output level
c. Control Source
d. Overtemp
5. Advanced circuit feedback shall include but not be limited to:
a. Load higher or lower than recorded value
b. DC detected on output
c. SCR failed on/off
d. Breaker trip
e. Module has been removed
f. Load failure