D) ARCHITECTURAL CONTROL PROCESSOR MODULES
1) The Architectural Control Processor shall be the Unison Paradigm P-ACP Series Control
Processor as manufactured by Electronic Theatre Controls, Inc., or equal.
2) The Architectural Control Processor (ACP) assembly shall be designed for use in DRd
Series Dimming Enclosures and ERn Series Control Enclosures.
3) The processor shall utilize microprocessor based, solid state technology to provide multi-
scene lighting and building control.
a) ACP shall support functions such as station programming, macro sequencing,
electronic lockout, room combine and astronomical time clock events. ACP
station processor shall allow configuration of the control system via the menus.
See software section for additional system details.
b) When used in a dimming enclosure, the ACP shall allow access to dimming control
menus including the status screen, dimming configuration screen, backup menu,
test menu and configuration menu.
4) One ACP shall be rated to drive 1024 channels of control, 1024 zones, 64 rooms, 512
presets, 62 button or button/fader stations and 6 Touchscreen Stations
5) ACP module electronics shall be convection cooled.
6) The ACP shall provide front-panel RJ45 jack, Secure Digital (SD) card slot, and Universal
Serial Bus (USB) Port for configuration and data exchange.
7) Architectural Lighting System configuration and program information shall be stored in flash
memory, which does not require battery backup.
8) The ACP shall be contained in a plug-in assembly and require no discrete wiring
connections; all wiring shall be terminated into Dimming or Control Enclosure.
a) The ACP shall support the following communications:
1) Echelon LinkPower
2) 10/100BaseTX, auto MDI/MDIX, 802.3af compliant Ethernet networking with
TCP/IP, ESTA BSR E1.17 Advanced Control Networks (ACN) and ESTA
BSR E1.31 (sACN) Protocols
3) EIA-232 serial protocol
4) ESTA DMX512A, configurable as input or output ports
5) Dry contact closure inputs
6) Dry contact closure outputs, rated at 1A@30VDC